Detecting AI Training in Datacentre Power

Tom Kimpson, Mauricio Baker and Emlyn Graham (University of Melbourne, University of Oxford, MATS) show that facility-level power metering can detect large training runs on a monitored cluster without trusting the operator, by tracking the iteration cadence of synchronous training.
Ask this paper
Method. A Viterbi tracker follows the wandering iteration frequency that synchronous training leaves in datacentre power draw.
Detection. On simulated power data with no hiding attempt, it detects at least 96% of training runs against a declared inference workload at a 1% false-alarm rate, within 0.04 of the Neyman-Pearson optimum, given a meter sampling at 2 Hz or faster.
Adversaries. Of eight hiding strategies, only extreme variation of work per iteration evades it. That strategy hides training in up to 73% of five-minute windows, but over a day at least 87% of runs are still caught at a 0.1% false-alarm rate per run.
Cost of hiding. The evading strategy costs no throughput, but in small-scale training it needs 93% to 267% more compute to reach the same loss.
Abstract
AI governance agreements require methods to detect large model training runs on a monitored computing cluster, without trusting the operator. We develop a method to detect synchronous model training in facility-level power by Viterbi tracking of the wandering iteration cadence. On simulated datacentre power, when the operator makes no attempt to hide, the Viterbi tracker detects at least $96\%$ of training runs against a declared inference workload, at a $1\%$ false-alarm rate and within $0.04$ of the Neyman--Pearson optimum, given a meter that samples at $2$ Hz or faster. Of eight adversarial strategies an operator might use to hide, only extreme variation of the work per iteration evades the tracker. Its strongest form hides training in up to $73\%$ of five-minute observations, but over a day at least $87\%$ of such runs are still caught, at a $0.1\%$ false-alarm rate per run. This adversarial strategy costs no throughput, but in small-scale training the operator needs $93$--$267\%$ more compute to reach the same loss. A modest passive meter is sufficient to make hidden training both detectable and expensive, which makes power metering a promising part of compute verification that does not depend on trusting the operator.